Click To Contact SunMaxx Solar Today

Design Resources: Laying Out The Solar Array

Find The Correct Layout For Your Solar Collector Array…

One of the biggest, most common, problems with solar thermal systems in the past has been incorrectly laid out collector arrays. In many cases, thermal expansion has caused pipe damage, and in others, excessive flow rates have caused erosion in the piping.

Needless to say, a properly laid out collector array will bring the performance of the collectors up to (or even above) design conditions and still maintain the the physical integrity of the system.

Our engineers have put together a list of key areas to pay attention to when laying out the collector array:

  • Keep the fluid velocity below 5 ft/sec. This is accomplished by having no row longer than 384" of collectors (width) with 1" headers or 576" of collectors (width) with 1.5" headers
  • You should allow for thermal expansion in the collector array and some "swing" between the header of the row and the supply and return piping
  • Always plumb each row in reverse-return style or allow for another method to balance the flow within the array
  • Insulate all lines and use UV protection (latex or jacketing is fine)
  • Use isolation valves to segregate each row in your array so that any row can be turned off and maintenanced while the rest of the continues to function

Open-Loop Array

Open Loop Array Layout

The image to the left shows a great standard layout for collectors with 1" headers – a typical 24 collectors in 3 rows of 8. The ball valves on the supply and return allow for the isolation of each row, and the lower header of each row has a pressure relief valve that can be used to relieve pressure and drain the row when needed. Automatic air vents allow trapped air to be purged as needed, and a thermal bleed valve that acts as a secondary freeze protection (in case the pumped recirculation fails) by allowing warmer mains water to flood through the row.

Closed-Loop Glycol Array

Closed-Loop Glycol Array Layout

The only difference between the closed-loop glycol array and the open-loop array is that the thermal bleed valve has been eliminated. Additionally, the air vent in a closed-loop glycol system can be manual instead of automatic because there is only a finite amount of air in the system that can be manually removed after startup the system sealed.

Drainback Array

Drainback Array Layout

The drainback array, as you can see, is the simplest of all because it doesn’t need a thermal bleed valve or air vents. Plus, there is no need for isolation valves on the collector rows because the loop is unpressurized and the fluid can’t flow against gravity back up into the collectors. In fact, the only valves are the isolation valves at the inlet of each row.

However, all piping in the drainback array must be sloped atleast 1/4" per foot so that the array can properly drain. All fittings and valves should be carefully located so that they do not restrict the ability of the array to drain under gravity.

Balancing The Flow Within Collector Rows

You should look to balance the flow between the rows of collectors in your commercial solar thermal arrays, but also balance the flow within each row of the array as well. This is important for a simple reason – studies have shown that collectors / rows with different flow rates generate as much as a 40F temperature difference. This temperature difference will create a significant decrease in output. These temperature differences are generally less in 8 collector rows, however, balancing should be attempted anyway.

Two Methods For Balancing The Flow Within Collector Rows

SunMaxx engineers recommend the following two methods for balancing the flow in your collector array rows.

The first method for balancing your flow is with ball valves. This is very simple – you can partially close the ball valves to level out the pressures between the top and bottom headers. You can use an IR gun to measure the covertemperatures of the collectors and when the temperatures are balanced, the flows should be as well.

Balancing Flows With Ball Valves

The second recommended method for balancing flows is to use a parallel-series method (split your 8 collector row into two parallel sets of 4 collectors – just plumb through the first 4 collectors in parallel, send it through a downtube and then plumb it through the next 4 collectors in parallel. this will nearly eliminate any flow differences. However, it will double the flow rate through each collector which will cause increased pressure drop (though it should not be enough to be a problem). Note – this method can not be used with drainback systems, but is great for open-loop and closed-lopp glycol systems.

Balancing Flows With Parallel-Series Method

Ready To Get Started? Need Assistance?
Call Our Solar Experts: 877.786.6299!
Example Dialog Text







Expected Timeline to purchase?:

Customer Type:

 

Please help us fight spam! What is the sum of 7 + 4?

 
Contact SunMaxx Solar SunMaxx Solar
Sales & Main Office
Rte 206
Bainbridge, NY 13733

P: 1.877.SUNMAXX
P: 1.877.786.6299
www.SunMaxxSolar.com