What is involved in setting the drainback option (ODB) on my SmartMaxx-DHWPlus controller?
What is involved in setting the drainback option (ODB) on my SmartMaxx-DHWPlus controller? In the submenu, switch ODB from “OFF” to “ON.” Four new items will appear in the submenu: tDTO, tFill, tSTB, and OBST. Some experimentation may be necessary to get these settings correct for your system.
- tDTO (time period switch-on) is the amount of time the DT O must be met before the controller will turn the pump on. The factory setting is 60 seconds. The collector/tank temperature differential must be met for 60 seconds straight before the controller will trigger the pump.
- tFill (filling time) is the amount of time the pump runs at 100% to push the heat transfer fluid up and over the top of the system piping. The factory setting is 5 minutes.
- tSTB (stabilization time) is the amount of time the controller will ignore the DT F after it changes over to minimum pump speed. The factory setting is 2 minutes. This time is set aside because running the pump at 100% may cool the collectors below the “off” temperature differential. So, instead of shutting the system down as soon as it comes on, tSTB allows a time period for the collectors to stabilize at the minimum pump speed.
- OBST (booster option) can be turned on if you have a second pump plumbed in series with the first. The second pump will then only come on during the filling time (tFill).
- The EM setting will be set to a fixed value of 200°F.
- DT O will be set to a fixed value of 20°F.
- DT F will be set to a fixed value of 8°F.
- DT S will be set to a fixed value of 30°F.